Abstract :
A number of measurements show the results of the harmonics and conducted emissions from “Energy-Savings” Compact Fluorescent Lamps (CFL) when connected to the power-line communications channel. Different CFL´s from different manufacturers were investigated. The paper covers the CENELEC band, as well as the broadband communications channel: 150kHz-30MHz. The obtained results show the levels of harmonics and interference that these types of lamps produce. It shows that CFL´s produce interference in the 3kHz-150kHz band, but this pose no risk for PLC. Some CFL´s do however produce interference in the 150kHz-30MHz band that can interfere with power-line communications.
Keywords :
broadband networks; carrier transmission on power lines; fluorescent lamps; interference; telecommunication channels; CENELEC band; CFL lamp; broadband communications channel; compact fluorescent lamp; energy saving; frequency 150 kHz to 30 MHz; interference; power-line communications channel; Current measurement; Electromagnetic compatibility; Fluorescent lamps; Harmonic analysis; Interference; Noise; Power harmonic filters; CFL; Compact Fluorescent Lamp; EMC; Harmonics; Interference; PLC; Powerline Communications; noise;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Line Communications and Its Applications (ISPLC), 2013 17th IEEE International Symposium on
Conference_Location :
Johannesburg
Print_ISBN :
978-1-4673-6014-2
Electronic_ISBN :
978-1-4673-6015-9
Type :
conf
DOI :
10.1109/ISPLC.2013.6525854
Filename :
6525854
Link To Document :
بازگشت