• DocumentCode
    604842
  • Title

    Development of a divided zone method for power savings in a data center

  • Author

    Ma, H.K. ; Chen, C.H.

  • Author_Institution
    Dept. of Mech. Eng., Nat. Taiwan Univ., Taipei, Taiwan
  • fYear
    2013
  • fDate
    17-21 March 2013
  • Firstpage
    33
  • Lastpage
    38
  • Abstract
    The number of data centers has increased continuously in recent years. The power required for a data center to cool its Information Technology (IT) equipment is typically approximately 35%~45% of the data center´s power consumption. In this study, a divided zone method is developed to improve the cooling efficiency for a data center. A divided zone partition can concentrate airflow for key components to avoid airflow bypass and to control different individual zones independently when a Fan Speed Control (FSC) is implemented for the system. At the server level, the Computational Fluid Dynamics (CFD) case study of a 1U server will be compared with and without the partition at an ambient temperature of 35°C. In the server system, the divided zone partition introduces the benefit of one specific zone to avoid airflow bypass and gain power savings. The partition can save 32.6% of the total fan power consumption and reduce the system airflow rate by 13.8%, which can also relieve the CRAH blower load. For a specific load change in the server, the FSC function can save 31.4% of the fan power consumption when the CPU load is decreased from 95 W to 76 W. Power savings can be enhanced from 31.4% to 46.8% after implementing the divided zone partition with a FSC function. Obviously, the divided zone partition can introduce extra cooling efficiency to save more power. When the divided zone method is applied in a data center room, it may enhance the server operating airflow by 39% for a specific 30% loading rack. In general, the utilization of a divided zone partition shows a significant power savings for IT equipment from the server level to the data center level.
  • Keywords
    computational fluid dynamics; cooling; energy conservation; fans; power aware computing; power consumption; thermal management (packaging); velocity control; CFD; CPU load; CRAH blower load; FSC function; IT equipment; airflow rate; computational fluid dynamics; cooling efficiency; data center power consumption; divided zone method; fan speed control; information technology; power 95 W to 76 W; power saving; server system; temperature 35 degC; zone partition; Atmospheric modeling; Computational fluid dynamics; Fans; Load modeling; Loading; Servers; CPU; Data center; cooling efficiency; divided zone; fan power;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Semiconductor Thermal Measurement and Management Symposium (SEMI-THERM), 2013 29th Annual IEEE
  • Conference_Location
    San Jose, CA
  • ISSN
    1065-2221
  • Print_ISBN
    978-1-4673-6427-0
  • Electronic_ISBN
    1065-2221
  • Type

    conf

  • DOI
    10.1109/SEMI-THERM.2013.6526802
  • Filename
    6526802