• DocumentCode
    60722
  • Title

    A Universal Islanding Detection Technique for Distributed Generation Using Pattern Recognition

  • Author

    Faqhruldin, Omar N. ; El-Saadany, Ehab F. ; Zeineldin, H.H.

  • Author_Institution
    Electr. & Comput. Eng. Dept., Univ. of Waterloo, Waterloo, ON, Canada
  • Volume
    5
  • Issue
    4
  • fYear
    2014
  • fDate
    Jul-14
  • Firstpage
    1985
  • Lastpage
    1992
  • Abstract
    Anti-islanding protection methods, proposed in the literature, are distributed generation (DG) type dependent or in other words work efficiently for a specific DG type (synchronous or inverter based). In this paper, we investigate the possibility of developing an efficient universal islanding detection method that can be applied to both inverter and synchronous-based DG. The proposed method relies on extracting a group of features, from measured data simulated for both types of DGs, from which the best features are selected for islanding detection. A random forest (RF) classification technique is used to detect islanding and non-islanding situations with an objective of minimizing the non-detection zone as well as avoiding nuisance DG tripping during non-islanding conditions. Islanding and non-islanding cases were generated for the IEEE 34-bus system and used to train and test the proposed technique. In the paper, k-fold cross-validation was used in order to test the accuracy of the proposed algorithm for detecting islanding. The results show that the proposed methodology has zero non-detection zone, high accuracy, and fast response when applied to both types of DGs independently of the size of the island. Among the various classification approaches investigated, the RF technique proved to be the most efficient approach for the proposed islanding detection method.
  • Keywords
    distributed power generation; pattern classification; power generation protection; random processes; DG type dependent; IEEE 34-bus system; RF technique; anti-islanding protection methods; distributed generation; inverter; k-fold cross-validation; nuisance DG tripping avoidance; pattern recognition; random forest classification technique; synchronous-based DG; universal islanding detection technique; zero nondetection zone; Accuracy; Feature extraction; Inverters; Islanding; Radio frequency; Reactive power; Vegetation; Decision tree; inverter-based distributed generator; islanding detection; naïve Bayes; neural network; random forest (RF); support vector machine (SVM); synchronous-based distributed generator;
  • fLanguage
    English
  • Journal_Title
    Smart Grid, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    1949-3053
  • Type

    jour

  • DOI
    10.1109/TSG.2014.2302439
  • Filename
    6839084