• DocumentCode
    6121
  • Title

    Secure Phase Comparison Schemes for Transmission-Line Protection Using Synchrophasors

  • Author

    Hinge, Trupti P. ; Dambhare, Sanjay S.

  • Author_Institution
    Dept. of Electr. Eng., Maharashtra Coll. of Eng., Nilanga, India
  • Volume
    30
  • Issue
    4
  • fYear
    2015
  • fDate
    Aug. 2015
  • Firstpage
    2045
  • Lastpage
    2054
  • Abstract
    The segregated phase comparison technique is a notable form of differential protection which compares the phase angle of end currents of a transmission line. The literature shows that phase differential protection serves as a better option for transmission-line protection due to its simplicity, sensitivity, selectivity and comprehensibility. However, line-charging current causes a significant error in the phase angle of two end currents of a transmission line. This paper presents improved phase comparison whichP compensates error due to line-charging current and a function of a cosine scheme using the equivalent- π model of the transmission line. The phase differential function is developed using phase coordinates. The scheme is compared with the existing scheme like, conventional scheme based on line currents, the positive-sequence component of line currents and a mixed combination of line currents. The global positioning system is used for time-synchronised measurements and fiber optics are considered for data communication. Simulations are carried out in an Alternate Transients Program/Electromagnetic Transients Program on an IEEE 14-bus system, and a protection scheme is implemented on one of the tie lines. The results demonstrate the accuracy of the proposed approach over the existing schemes.
  • Keywords
    IEEE standards; phasor measurement; power transmission lines; power transmission protection; IEEE 14-bus system; alternate transients program; data communication; electromagnetic transients program; fiber optics; line-charging current; phase comparison technique; phase differential function; phase differential protection; secure phase comparison schemes; synchrophasors; time-synchronised measurements; transmission line; transmission-line protection; Circuit faults; Current measurement; Fault currents; Power transmission lines; Relays; Time measurement; Transmission line measurements; Segregated phase comparison; synchronized measurements; transmission lines;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2015.2417997
  • Filename
    7072513