• DocumentCode
    615550
  • Title

    Influence of temperature on frequency response analysis of transformer winding

  • Author

    Bagheri, Mehdi ; Phung, B.T. ; Blackburn, Trevor ; Naderian, Ali

  • Author_Institution
    Univ. of New South Wales, Sydney, NSW, Australia
  • fYear
    2013
  • fDate
    2-5 June 2013
  • Firstpage
    40
  • Lastpage
    44
  • Abstract
    Frequency Response Analysis (FRA) has been operated since last decade as a sensitive method in transformer internal defect recognition. This study has concentrated on influence of temperature variation of the transformer winding on FRA trace. An oil-free single phase model transformer involving concentric LV and HV windings is taken as a test object. The test object temperature is changed widely from low to high temperatures and the frequency response traces of the windings are recorded. In addition, a pair of winding discs including oil filled metal container is taken as another test object and its frequency response traces are recoded for various temperatures. FRA traces deviations as well as total capacitance variation due to the temperature changes in transformer windings are elaborated and discussed.
  • Keywords
    frequency response; transformer windings; capacitance variation; concentric HV windings; concentric LV windings; frequency response analysis; oil filled metal container; oil-free single phase model transformer; transformer internal defect recognition; transformer winding; Capacitance; Frequency response; Moisture; Oil insulation; Power transformer insulation; Resonant frequency; Windings; Frequency response analysis; Moisture content; Temperature; Transformer diagnosis;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation Conference (EIC), 2013 IEEE
  • Conference_Location
    Ottawa, ON
  • Print_ISBN
    978-1-4673-4738-9
  • Electronic_ISBN
    978-1-4673-4739-6
  • Type

    conf

  • DOI
    10.1109/EIC.2013.6554198
  • Filename
    6554198