• DocumentCode
    615578
  • Title

    An optimal surge arrester for EHV air insulated stations utilizing high-gradient MO resistors

  • Author

    Stenstrom, L. ; Taylor, James ; Westerlund, H.

  • Author_Institution
    ABB AB High Voltage Components, Ludvika, Sweden
  • fYear
    2013
  • fDate
    2-5 June 2013
  • Firstpage
    201
  • Lastpage
    205
  • Abstract
    The use of high-gradient (HGR) MO resistors makes it possible to significantly reduce the length of surge arresters for air insulated substations (AIS). The optimal length would be to use HGR MO resistors which exactly fill up the necessary length needed to obtain a sufficient margin between arrester protection level and the voltage withstand of the housing. However, this would require a design with excellent thermal properties which could handle the increased power losses per unit length and higher temperature after energy absorption. This paper describes a surge arrester design in accordance with this concept. Furthermore, the requirements, type tests performed to verify the design and experience from a three and a half year field installation with supervision of the arrester leakage current are presented.
  • Keywords
    arresters; leakage currents; resistors; substation protection; EHV air insulated stations; air insulated substations; arrester leakage current; energy absorption; high-gradient MO resistors; surge arrester design; Arresters; Current measurement; Leakage currents; Resistors; Stress; Surges; AIS; MO resistor; condition monitoring; high-gradient; insulation withstand; surge arrester;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation Conference (EIC), 2013 IEEE
  • Conference_Location
    Ottawa, ON
  • Print_ISBN
    978-1-4673-4738-9
  • Electronic_ISBN
    978-1-4673-4739-6
  • Type

    conf

  • DOI
    10.1109/EIC.2013.6554233
  • Filename