DocumentCode :
615614
Title :
Optimization of corona ring design for a 400KV non-ceramic insulator
Author :
Al Murawwi, Esam ; Mohammed, Arshad ; Alip, Zapaer ; El-Hag, Ayman
Author_Institution :
Power Eng. & Commissioning, TRANSCO, Abu Dhabi, United Arab Emirates
fYear :
2013
fDate :
2-5 June 2013
Firstpage :
370
Lastpage :
373
Abstract :
In this paper, a corona ring design optimization for a 400kV non-ceramic insulator was investigated. Two parameters were changed during the study which are: the ring diameter (R) and the diameter of the ring tube (r). In this study, with the aid of a developed mathematical model the maximum electric field curves were recreated and an estimated electric field equation in terms of r and R while fixing H was found. Finally, using the estimated equation, a non-linear optimization technique was applied. The solution for this optimization problem gives the optimal dimensions of r and R as well as the ratio of R/r which will reduce the electric field value most effectively for a given constant cost.
Keywords :
corona; electric fields; insulators; optimisation; corona ring design; electric field curves; electric field equation; mathematical model; nonceramic insulator; optimization; Corona; Electric fields; Electron tubes; Equations; Insulators; Mathematical model; Optimization; Corona ring; Mathematical Model; Non-linear optimization; Rate of changes;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation Conference (EIC), 2013 IEEE
Conference_Location :
Ottawa, ON
Print_ISBN :
978-1-4673-4738-9
Electronic_ISBN :
978-1-4673-4739-6
Type :
conf
DOI :
10.1109/EIC.2013.6554269
Filename :
6554269