Abstract
This paper presents an algorithm for high impedance fault (HIF) detection by phasor measurement units (PMUs) that are basic elements in wide area monitoring and protection systems (WAMPS). This method uses output current phasors of PMU for detection of HIF. At first, change of current detects by summation of errors between sampled data and estimated samples that are obtained from output phasors of PMU,Then in order to certain that this change is HIF, 3rd harmonic phase of fault current is used to discriminate HIF from normal condition such as load increasing/decreasing. Effects of transformer vector group on 3r harmonic phase are also studied. Several cases are simulated in EMTP&MATLAB to evaluate accuracy of method.
Keywords
phasor measurement; power distribution faults; power transformers; EMTP; HIF detection; Matlab; PMU application; WAMPS; distribution network high impedance fault detection; phasor measurement units; transformer vector group; wide area monitoring and protection systems; Conductors; Harmonic analysis; Impedance; Measurement units; Switches; Transforms; Vectors; 3rd harmonic phase; Transformer vector group; high impedance fault; phasor measurement units;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Power Distribution Networks (EPDC), 2013 18th Conference on
Conference_Location
Kermanshah
Print_ISBN
978-1-4799-0092-3
Type
conf
DOI
10.1109/EPDC.2013.6565973
Filename
6565973
Link To Document