DocumentCode
62816
Title
A Novel Backup Distance Protection Scheme for Series-Compensated Transmission Lines
Author
Hashemi, S.M. ; Hagh, Mehrdad Tarafdar ; Seyedi, Heresh
Author_Institution
Fac. of Electr. & Comput. Eng., Univ. of Tabriz, Tabriz, Iran
Volume
29
Issue
2
fYear
2014
fDate
Apr-14
Firstpage
699
Lastpage
707
Abstract
Conventional distance protection applies the positive-sequence impedance to protect a line against short-circuit faults. Series-compensated lines may considerably change the positive-sequence impedance of the fault path and cause the distance relays to maloperate. To overcome this problem, the mutual impedance between phases of a transmission line is used for the design of a new distance protection scheme. The voltages and currents of both ends of the line are applied to compute the mutual impedance between the relay and the fault point. The proposed scheme has a reliable performance in protection against single-phase and double-phase-to-ground faults and, therefore, it can be used as a backup protection. Simulation results approve the efficiency of the proposed method in protection of series-compensated transmission lines.
Keywords
power transmission faults; power transmission lines; power transmission protection; relay protection; short-circuit currents; backup distance protection scheme; backup protection; distance relays; double-phase-to-ground faults; fault path; fault point; mutual impedance; positive-sequence impedance; series-compensated transmission lines protection; short-circuit faults; single-phase-to-ground faults; Circuit faults; Impedance; Power transmission lines; Protective relaying; Resistance; Transmission line measurements; Distance protection; mutual impedance; series compensation; transmission line;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2013.2272765
Filename
6571287
Link To Document