Influence of auxiliary electrode arrangements on earth resistance measurement using the Fall-of-Potential method
Author :
Ladanyi, Jozsef ; Smohai, Balazs
Author_Institution :
Dept. of Power Syst. Eng., Budapest Univ. of Technol. & Econ., Budapest, Hungary
fYear :
2013
fDate :
6-8 June 2013
Firstpage :
1
Lastpage :
6
Abstract :
This paper deals with the earth resistance measurement using the Fall-of-Potential method and its measurement errors on site measurements. Numerical results are presented in case of a substation and a transmission line tower grid, for various soil structures and auxiliary earth electrode directions. The actual regulations for the place of the potential probe and the distance for the current electrode in the interest of the accurate measurement are analyzed and compared to the standards´ specification. A detailed study is done about the specified and other, typical, possible electrode arrangements. The results of the simulations can significantly help the colleagues´ work in reference to resistance to earth measurements.
Keywords :
earthing; electric resistance measurement; electrodes; measurement errors; power transmission lines; power transmission protection; substation protection; auxiliary earth electrode direction; auxiliary electrode arrangement; earth resistance measurement; fall-of-potential method; measurement errors; site measurements; soil structure; substation; transmission line tower grid; Current measurement; Earth; Electrical resistance measurement; Electrodes; Grounding; Measurement errors; Soil; Fall-of-potential method; measurement error; resistance to earth; site measurement;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Energy (IYCE), 2013 4th International Youth Conference on
Conference_Location :
Sio??fok
Type :
conf
DOI :
10.1109/IYCE.2013.6604146
Filename :
6604146
Link To Document :
بازگشت