  • Abstract
    The number of the faults caused by AC filters has been reached 8 times in a HVDC system of CSG. The AC Filter may produce inrush current and over-voltage when switching on, which will occasionally damage the filters, make protection malfunction and threat the system. The paper introduces a simulation based on Monte Carlo algorithm and PSCAD User-definition model in order to analysis the problem. This paper makes simulations about inrush current and the zero sequence current to research three-phase unbalanced inrush current in the inverter side. Based on these results, some methods which solve the effect of inrush current has been proposed, like erecting POW, locking the unbalanced protection temporarily.
  • Keywords
    HVDC power transmission; Monte Carlo methods; invertors; overvoltage protection; power filters; CSG; HVDC AC filters; HVDC system; Monte Carlo algorithm; POW; PSCAD user-definition model; inverter side; over-voltage; protection malfunction; three-phase unbalanced inrush current; zero sequence current; Capacitors; Filtering algorithms; HVDC transmission; Power harmonic filters; Surge protection; Surges; Switches; AC Filter; Monte Carlo Algorithm; Unbalanced Current; User-definition Mode;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Engineering and Automation Conference (PEAM), 2012 IEEE
  • Conference_Location
    Wuhan
  • Print_ISBN
    978-1-4577-1599-0
  • Type

    conf

  • DOI
    10.1109/PEAM.2012.6612528
  • Filename
    6612528