• DocumentCode
    63888
  • Title

    Partial discharge initiated by free moving metallic particles on GIS insulator surface: severity diagnosis and assessment

  • Author

    Bo Qi ; Chengrong Li ; Zhaoliang Xing ; Zhen Wei

  • Author_Institution
    State Key Lab. of Alternate Electr. Power Syst. with Renewable Energy Sources, North China Electr. Power Univ., Beijing, China
  • Volume
    21
  • Issue
    2
  • fYear
    2014
  • fDate
    Apr-14
  • Firstpage
    766
  • Lastpage
    774
  • Abstract
    Free moving metallic particles are one of the most common defects leading to insulation failures in gas insulated substation (GIS) equipment. The present research is designed to diagnose and assess the severity levels of partial discharge (PD) initiated by free moving metallic particles on GIS insulator surface. On a well-established 252 kV GIS experiment platform, long term tests were conducted to observe the entire development process of partial discharge from its very initiation stage till eventual flashover as the applied voltage gradually boosted. Real time measurement was undertaken during the tests to capture the trend curve of partial discharge as a result of test time, scatter plot, histogram, grey-scale map, and time-frequency map of partial discharge. The experimental results indicate that 1) partial discharge provoked by free moving metallic particles in GIS goes through three severity levels, namely, minor discharge, moderate discharge, and threatening discharge; 2) as partial discharge develops, the phase distribution is widening and corresponding shape changes occur in the scatter plot, histogram, grey-scale map, and time-frequency map. It is recommended that the features of phase distribution and the corresponding spectra could be used as important criteria in diagnosing and assessing the severity levels of partial discharge initiated by free moving metallic particles on GIS insulator surface.
  • Keywords
    gas insulated substations; insulators; partial discharges; GIS insulator surface; defects; free moving metallic particles; gas insulated substation; grey-scale map; histogram; insulation failures; partial discharge; phase distribution; real time measurement; scatter plot; severity assessment; severity diagnosis; severity levels; test time; time-frequency map; voltage 252 kV; Discharges (electric); Flashover; Gas insulation; Insulators; Partial discharges; Photonics; Surface discharges; Gas insulated substation; diagnosis and assessment; free moving metallic particles; insulator; partial discharge; severity;
  • fLanguage
    English
  • Journal_Title
    Dielectrics and Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    1070-9878
  • Type

    jour

  • DOI
    10.1109/TDEI.2013.003585
  • Filename
    6783071