• DocumentCode
    645001
  • Title

    Installation and maintenance challenges of NEMA Type 7 hazardous area enclosures

  • Author

    Manahan, Joseph M. ; Zhao, Yiwen ; Foster, M. ; Deegan, Joseph T.

  • Author_Institution
    Cooper Crouse-Hinds, Syracuse, NY, USA
  • fYear
    2013
  • fDate
    23-25 Sept. 2013
  • Firstpage
    1
  • Lastpage
    10
  • Abstract
    National Electrical Manufacturers Association (NEMA) Type 7 explosion-proof enclosures are widely regarded for their robust construction and dependable operation. These enclosures are sustained without the additional safety systems required to ensure operation of a purged and pressurized piece of equipment. Similarly, NEMA Type 7 enclosures are maintained without the costly component inventory which may be required to ensure maximum uptime of non-serviceable encapsulated equipment. NEMA Type 7 enclosures are generally constructed of cast aluminum or iron-based materials and are capable of withstanding numerous explosive events. NEMA Type 7 enclosures ensure hazardous area safety by extinguishing the flame through precision machined surfaces and controlling structural deformation should an explosive event occur. If maintenance practices are not designed to ensure the integrity of the enclosure, repeated access to internal equipment and oxidation of critical surfaces may lead to the loss of the enclosure´s explosion-proof protection. The paper reviews maintenance best practices and common errors with their potential consequences. The likelihood of error may be reduced by employing a variety of available technologies. Each technology will be explained based on case study examples to illustrate the reduction in total cost of ownership for equipment when best practices are observed.
  • Keywords
    deformation; explosion protection; hazardous areas; maintenance engineering; safety systems; NEMA type 7 explosion-proof enclosures; NEMA type 7 hazardous area enclosures; National Electrical Manufacturers Association; cast aluminum; critical surface oxidation; enclosure explosion-proof protection; explosive events; flame; hazardous area safety; iron-based materials; nonserviceable encapsulated equipment; precision machined surfaces; safety systems; structural deformation control; total cost of ownership; Atmosphere; Fasteners; Fires; Ignition; Maintenance engineering; Temperature; Torque; /ndex Terms; Corrosion; Deflection; Explosion-proof; Flame-path; Flame-proof; Moisture; NEMA Type 7;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Petroleum and Chemical Industry Technical Conference (PCIC), 2013 Record of Conference Papers Industry Applications Society 60th Annual IEEE
  • Conference_Location
    Chicago, IL
  • ISSN
    0090-3507
  • Print_ISBN
    978-1-4673-5108-9
  • Type

    conf

  • DOI
    10.1109/PCICon.2013.6666049
  • Filename
    6666049