DocumentCode :
647787
Title :
Online monitoring of substation grounding grid conditions using touch and step voltage sensors
Author :
Xun Long ; Ming Dong ; Wilsun Xu ; Yunwei Li
Author_Institution :
Univ. of Alberta, Edmonton, AB, Canada
fYear :
2013
fDate :
21-25 July 2013
Firstpage :
1
Lastpage :
1
Abstract :
Summary form only given: A grounding grid of a substation is essential for reducing the ground potential rises inside and outside the substation during a short-circuit event. The performance of a grounding grid is affected by a number of factors, such as the soil conductivity and grounding rod corrosion. Industry always has a strong desire for a reliable and cost-effective method to monitor the condition of a grounding grid to ensure personnel safety and prevent equipments damage. In view of the increased adoption of telecom and sensor technologies in power industry through the smart grid initiative, this paper proposes an online condition monitoring scheme for grounding grids. The scheme monitors touch and step voltages in a substation through a sensor network. The voltages are created by a continuously-injected, controllable test current, which is generated by a pair of thyristors. The results are transmitted to a database through wireless telecommunication.
Keywords :
condition monitoring; earthing; electricity supply industry; measurement systems; smart power grids; substations; wireless sensor networks; database; grid performance; grounding rod corrosion; historical data; measurement techniques; online condition monitoring scheme; personnel safety; power industry; sensor network; sensor technologies; short-circuit event; smart grid initiative; soil conductivity; step voltage sensors; substation grounding grid conditions; thyristors; touch voltage sensors; wireless telecommunication; Databases; Grounding; Intelligent sensors; Monitoring; Substations; Tactile sensors;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power and Energy Society General Meeting (PES), 2013 IEEE
Conference_Location :
Vancouver, BC
ISSN :
1944-9925
Type :
conf
DOI :
10.1109/PESMG.2013.6672322
Filename :
6672322
Link To Document :