DocumentCode
647913
Title
Differential power based symmetrical fault detection during power swing
Author
PRADHAN, ASHOK KUMAR ; Rao, Ganeswara
Author_Institution
Electr. Eng., Indian Inst. of Technol., India
fYear
2013
fDate
21-25 July 2013
Firstpage
1
Lastpage
1
Abstract
Summary form only given. Distance relays are blocked during power swing to ensure reliability of the power system. However, if a fault occurs during power swing, it should be detected and unblocking function should be invoked to clear the fault as soon as possible. Due to symmetric nature of signals during power swing, symmetrical faults are difficult to be detected. In this paper, a differential power based fault detection technique is proposed for detection of symmetrical faults during power swing. The differential power is calculated from the difference in predicted and actual samples of voltage and current. The predicted voltage and current samples are obtained using autoregression technique. The proposed method is tested for different fault conditions and the results are compared with the available method. Proposed method is found to identify symmetrical faults accurately during slow and fast power swings for different power systems.
Keywords
autoregressive processes; fault diagnosis; power system faults; power system reliability; autoregression technique; current samples; differential power based symmetrical fault detection technique; distance relays; fault conditions; power swing; power system reliability; symmetrical fault identification; voltage samples; Electrical fault detection; Fault detection; Power system reliability; Protective relaying; Reliability engineering;
fLanguage
English
Publisher
ieee
Conference_Titel
Power and Energy Society General Meeting (PES), 2013 IEEE
Conference_Location
Vancouver, BC
ISSN
1944-9925
Type
conf
DOI
10.1109/PESMG.2013.6672463
Filename
6672463
Link To Document