Abstract :
This document describes the modelling of the 400 kV up-stream network for the energization of a 340 MVA transformer, using a Thevenin equivalent and also its detailed representation; after the validation of the complete network under steady-state conditions, a comparison between measurements made on site and transient simulations have also been performed, giving very satisfactory results, especially when a detailed modelling of the network is considered, as the transformer considered is highly non linear; non linear aspects are discussed.
Keywords :
equivalent circuits; power transformers; Thevenin equivalent; apparent power 340 MVA; power transformer; steady-state condition; upstream network representation; voltage 400 kV; Circuit faults; Integrated circuit modeling; Power transformer insulation; Resonant frequency; Substations; Surges; energization; modeling; saturation; transformer; upstream network;