• DocumentCode
    648303
  • Title

    Using synchronized wide area measurements for response-based switched reactive controls

  • Author

    Quint, Ryan D. ; Kosterev, Dmitry N. ; Heredia, Eric M.

  • Author_Institution
    Transm. Planning, Bonneville Power Adm., Vancouver, BC, Canada
  • fYear
    2013
  • fDate
    21-25 July 2013
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    BPA and WECC utilities are investing resources in phasor measurement technologies and advanced applications utilizing synchronized data. The new production-grade synchrophasor infrastructure opens up opportunities for expanding existing response-based stability controls. A synchrophasor-based RAS scheme is proposed that utilizes both real power and phase angle difference rate-of-change to detect large disturbances and contingencies. The algorithm is applied to a prospective reactive switching scheme for the Bonneville Power Administration. The controller performance is simulated against historic disturbance events.
  • Keywords
    phasor measurement; power system dynamic stability; phase angle difference rate of change; phasor measurement technology; power system stability; production-grade synchrophasor infrastructure; reactive switching scheme; response-based stability control; response-based switched reactive controls; synchronized wide area measurements; Control systems; Phasor measurement units; Power system stability; Stability analysis; Synchronization; Thermal stability; power system dynamic performance; power system stability; power system stability controls; synchrophasors;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power and Energy Society General Meeting (PES), 2013 IEEE
  • Conference_Location
    Vancouver, BC
  • ISSN
    1944-9925
  • Type

    conf

  • DOI
    10.1109/PESMG.2013.6672877
  • Filename
    6672877