• DocumentCode
    653706
  • Title

    Power grid fault traveling wave network location method

  • Author

    Li Zewen ; Hua Huanhuan ; Deng Feng ; Zeng Xiangjun ; Yu Kun

  • Author_Institution
    Hunan Province Key Lab. of Smart Grids Oper. & Control, Changsha Univ. of Sci. & Technol., Changsha, China
  • fYear
    2013
  • fDate
    6-11 Oct. 2013
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    Traditional fault traveling wave location schemes, which are based on the fault information of only one line, have lower sensitivity and reliability, especially when one or more traveling wave fault location devices (TWFLD) break down, startup failure or record wrong arrival time of traveling wave, this will result in the failure of the fault location. Based on the analysis of the propagation characteristics of the fault traveling wave in power grid, a novel power grid fault traveling wave network location method is proposed in this paper. In this method, the recorded arrival time of the initial fault traveling waves in all substations can be used effectively by information fusion technology, and the fault point is located by the power grid fault traveling wave network location method. This method can achieve fault location even when one or more TWFLD break down, startup failure or record wrong arrival time of the initial traveling wave. The simulation results match the theoretical analysis well and show that the proposed location method provides not only high accuracy and reliability, but also good economy. These characteristics are beneficial to further enhancement of the practicability of the traveling wave location.
  • Keywords
    power grids; power system faults; power system reliability; substations; TWFLD; fault information; fault traveling wave; information fusion technology; power grid fault; propagation characteristics; recorded arrival time; reliability; startup failure; substations; traveling wave fault location devices; traveling wave location; traveling wave network location; Circuit faults; Fault location; Power grids; Substations; Transient analysis; Fault location; Global Positioning System; Power system faults; Power system protection; network location; the initial traveling wave; traveling wave;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Industry Applications Society Annual Meeting, 2013 IEEE
  • Conference_Location
    Lake Buena Vista, FL
  • ISSN
    0197-2618
  • Type

    conf

  • DOI
    10.1109/IAS.2013.6682615
  • Filename
    6682615