Title :
Demonstration of a low-cost fault detector for sum current measurement of overhead MV lines
Author :
Rimminen, Henry ; Seppa, Heikki ; Kostiainen, Antti
Author_Institution :
Sensors & Wireless Devices - MEMSSensors, VTT Tech. Res. Centre of Finland, Espoo, Finland
Abstract :
We present field test results of a low-cost fault detector for medium voltage power lines. Three devices are clamped on the lines and measure current with induction coils up to 190 A. The sensors harvest energy inductively from the line current. They are synchronized by radio and sum current of three phases is calculated. We compared the measured sum current with a substation reading during earth faults. With fault resistances between 0 - 5000 Ω the full scale error of sum current was between 0.2 - 4.0 %. In a normal state the maximum error was 2.6 %. Earth faults up to 330 Ω were detectable. The energy harvesting provided adequate operating power for the tests, but not yet for continuous operation.
Keywords :
earthing; electric current measurement; electric sensing devices; energy harvesting; fault diagnosis; power cables; power overhead lines; earth faults; energy harvesting; induction coils; line current; low-cost fault detector; medium voltage power lines; overhead MV lines; sensors; substation reading; sum current measurement; Batteries; Circuit faults; Current measurement; Detectors; Earth; Electrical resistance measurement; Current measurement; Energy harvesting; Fault detection; Power distribution faults;
Conference_Titel :
Innovative Smart Grid Technologies Europe (ISGT EUROPE), 2013 4th IEEE/PES
Conference_Location :
Lyngby
DOI :
10.1109/ISGTEurope.2013.6695259