Title :
Sampled values packet loss impact on IEC 61850 distance relay performance
Author :
Ali, Imran ; Thomas, Mini S. ; Gupta, Swastik
Author_Institution :
Dept. of Electr. Eng., Jamia Millia Islamia, New Delhi, India
Abstract :
Modern substations are implementing Switched Ethernet based IEC 61850-9-2 Process bus communication networks for realizing their protection functions. Packet loss is a common phenomenon and plays a crucial role in the implementation of communication network based time-critical real time protection applications of power system. This paper presents the modeling and simulation of communication based digital distance relay protection scheme using MATLAB. In the first phase, the scheme is tested under various fault types, locations and fault resistance conditions to verify the operating performance of simulated distance relay model. In second phase, it is tested under sampled values packets loss condition to analyze the impact of lost data on the trip time performance of relay model. The result shows that the lost sampled values data in input signals adversely affects the tripping of distance relay.
Keywords :
IEC standards; fault location; relay protection; substation protection; IEC 61850 distance relay performance; MATLAB; communication based digital distance relay protection scheme; fault locations; fault resistance conditions; fault types; packets loss condition; sampled values packet loss; trip time performance; Circuit faults; IEC standards; Impedance; Mathematical model; Power systems; Protective relaying; Communication Schemes; Distance Protection; IEC 61850 Substation Automation System (SAS); IEC 61850-9-2 Process Bus; Switched Ethernet;
Conference_Titel :
Innovative Smart Grid Technologies - Asia (ISGT Asia), 2013 IEEE
Conference_Location :
Bangalore
Print_ISBN :
978-1-4799-1346-6
DOI :
10.1109/ISGT-Asia.2013.6698767