• DocumentCode
    666029
  • Title

    Synchronization of grid-connected renewable energy sources under highly distorted voltages and unbalanced grid faults

  • Author

    Hadjidemetriou, Lenos ; Kyriakides, Elias ; Blaabjerg, Frede

  • Author_Institution
    Dept. of Electr. & Comput. Eng., Univ. of Cyprus, Nicosia, Cyprus
  • fYear
    2013
  • fDate
    10-13 Nov. 2013
  • Firstpage
    1887
  • Lastpage
    1892
  • Abstract
    Renewable energy sources require accurate and appropriate performance not only under normal grid operation but also under abnormal and faulty grid conditions according to the modern grid codes. This paper proposes a novel phase-locked loop algorithm (MSHDC-PLL), which can enable the fast and dynamic synchronization of the interconnected renewable energy system under unbalanced grid faults and under highly harmonic distorted voltage. The outstanding performance of the suggested PLL is achieved by implementing an innovative multi-sequence/harmonic decoupling cell in order to dynamically cancel out the oscillation of the positive sequence voltage vector, produced by the existence of unbalanced and harmonic distorted voltage. The fast and accurate response of the proposed PLL under abnormal grid conditions is very important for the appropriate synchronization and control of the interconnected renewable energy systems. Therefore, the performance of the new PLL can increase the quality of the injected power under abnormal conditions and in addition enable the renewable energy systems to provide the appropriate support to the grid under balanced and unbalanced grid faults.
  • Keywords
    harmonic oscillators; phase locked loops; power generation faults; power grids; power supply quality; power system harmonics; power system interconnection; renewable energy sources; synchronisation; MSHDC-PLL; abnormal grid conditions; faulty grid conditions; grid codes; grid-connected renewable energy source synchronization; harmonic decoupling cell; highly harmonic distorted voltage; interconnected renewable energy system synchronization; multisequence decoupling cell; phase-locked loop algorithm; positive sequence voltage vector oscillation; unbalanced grid faults; Harmonic analysis; Harmonic distortion; Oscillators; Phase locked loops; Power harmonic filters; Synchronization; Vectors; distorted voltage; fault ride through operation; grid side converter; grid synchronization; interconnected renewable energy systems; phase-locked loop; unbalanced grid faults;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Industrial Electronics Society, IECON 2013 - 39th Annual Conference of the IEEE
  • Conference_Location
    Vienna
  • ISSN
    1553-572X
  • Type

    conf

  • DOI
    10.1109/IECON.2013.6699419
  • Filename
    6699419