  • Abstract
    This work explores the salt fog test to evaluate the performance of glass insulators used in a 230 kV transmission line. Three types of glass insulators were used, from the field with original contamination, a clean one, and a RTV coated one. The results have demonstrated that the pre-contamination have a role in salt fog performance and that the RTV coated insulator has shown least leakage current and was the last to fail in the salt fog.
  • Keywords
    fog; glass; insulators; materials testing; power transmission lines; RTV coated insulator; contamination; glass insulators performance; leakage current; salt fog performance; salt fog testing; surface conditions; transmission line; voltage 230 kV; Contamination; Glass; Insulators; RTV coating; contamination performance; glass insulator; leakage current; salt fog;