Industrial Static Synchronous Compensator (STATCOM) is typically applied at or near the load center to mitigate voltage fluctuation, flicker, phase unbalance, non-sine distortion or other load-related disturbance. Special attention is paid to the influence of grid negative sequence voltage to STATCOM current, the unbalance of grid voltage causes not only the AC current unbalance but also the DC voltage fluctuation. In order to let the inverter voltage contain the fundamental negative sequence component corresponding to the grid voltage, a new dual-loop control scheme is proposed to suppress the influence in this paper. The negative sequence voltage decomposition algorithm is also introduced. The validity of all analyses is verified by the simulation.
Keywords :
invertors; power grids; static VAr compensators; AC current unbalance; DC voltage fluctuation; STATCOM current; dual-loop control scheme; grid voltage; industrial static synchronous compensator; inverter voltage; load-related disturbance mitigation; negative sequence voltage decomposition algorithm; non-sine distortion mitigation; phase unbalance mitigation; voltage flicker mitigation; voltage fluctuation mitigation; Automatic voltage control; Fluctuations; Gold; Inductors; Integrated circuits; Voltage fluctuations; STATCOM; dual-loop control; impact; negative sequence; unbalance;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Machines and Systems (ICEMS), 2013 International Conference on
Conference_Location :
Busan
Print_ISBN :
978-1-4799-1446-3
Type :
conf
DOI :
10.1109/ICEMS.2013.6713344
Filename :
6713344
Link To Document :
بازگشت