Abstract :
A fault-transient synchrophasor is computed over a window of pre-fault and fault samples. A fault synchrophasor is computed over a window of fault samples only. Fault-transient synchrophasors are discarded and are generally not used in the synchrophasor applications. Recently, an algorithm has been proposed to compute fault synchrophasor from fault-transient synchrophasor in phasor data concentrator (PDC). The accuracy of the existing algorithm deteriorates due to fault-induced transients and inaccurate fault starting time. A robust algorithm has been proposed to compute fault synchrophasor from fault-transient synchrophasor in PDC. The proposed algorithm does not use fault starting time in the calculations. It also performs better than the existing algorithm when fault-induced transients are present in the signal. The proposed algorithm is simple, non-iterative and performs satisfactorily in various investigated scenarios. The advantage of the proposed algorithm has been demonstrated in the context of fault location application.
Keywords :
fault location; phasor measurement; power system transients; PDC; fault location application; fault-induced transients; fault-transient synchrophasor; noniterative algorithm; phasor data concentrator; robust algorithm; synchrophasor fault estimation;
fLanguage :
English
Journal_Title :
Generation, Transmission & Distribution, IET
Publisher :
iet
ISSN :
1751-8687
Type :
jour
DOI :
10.1049/iet-gtd.2014.0100
Filename :
7042453
Link To Document :
بازگشت