• DocumentCode
    679481
  • Title

    Influence of low-voltage line on sparkover rate of 6.6 kV distribution line

  • Author

    Michishita, Koji ; Yokoyama, Shiyoshi ; Ujihashi, Kazuyuki ; Sakai, Ryuichi ; Furukawa, S.

  • Author_Institution
    Dept. of Electr. & Electron. Eng., Shizuoka Univ., Hamamatsu, Japan
  • fYear
    2013
  • fDate
    7-11 Oct. 2013
  • Firstpage
    225
  • Lastpage
    230
  • Abstract
    In this paper, the authors discuss the influence of the low-voltage distribution line for power and light on the sparkover rate of 6.6 kV power distribution line based on the numerical calculation by the EMTP. The low-voltage distribution line installed below the 6.6 kV distribution line contributes to the decrease of the sparkover rate of the 6.6 kV line mainly due to the branching effect to the lightning current in case of direct strokes to the 6.6kV line including the concrete pole.
  • Keywords
    poles and towers; power distribution lines; sparks; EMTP; concrete pole; direct strokes; lightning current; low-voltage distribution line; numerical calculation; power distribution line; sparkover rate; voltage 6.6 kV; Arresters; Concrete; Flashover; Grounding; Lightning; Surges; Wires; OGHW (overhead ground wire); concrete pole; direct stroke; power distribution line; sparkover rate; surge arrester;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Lightning Protection (XII SIPDA), 2013 International Symposium on
  • Conference_Location
    Belo Horizonte
  • Print_ISBN
    978-1-4799-1343-5
  • Type

    conf

  • DOI
    10.1109/SIPDA.2013.6729201
  • Filename
    6729201