Influence of low-voltage line on sparkover rate of 6.6 kV distribution line
Author
Michishita, Koji ; Yokoyama, Shiyoshi ; Ujihashi, Kazuyuki ; Sakai, Ryuichi ; Furukawa, S.
Author_Institution
Dept. of Electr. & Electron. Eng., Shizuoka Univ., Hamamatsu, Japan
fYear
2013
fDate
7-11 Oct. 2013
Firstpage
225
Lastpage
230
Abstract
In this paper, the authors discuss the influence of the low-voltage distribution line for power and light on the sparkover rate of 6.6 kV power distribution line based on the numerical calculation by the EMTP. The low-voltage distribution line installed below the 6.6 kV distribution line contributes to the decrease of the sparkover rate of the 6.6 kV line mainly due to the branching effect to the lightning current in case of direct strokes to the 6.6kV line including the concrete pole.
Keywords
poles and towers; power distribution lines; sparks; EMTP; concrete pole; direct strokes; lightning current; low-voltage distribution line; numerical calculation; power distribution line; sparkover rate; voltage 6.6 kV; Arresters; Concrete; Flashover; Grounding; Lightning; Surges; Wires; OGHW (overhead ground wire); concrete pole; direct stroke; power distribution line; sparkover rate; surge arrester;