• DocumentCode
    683324
  • Title

    Conversion efficiencies of six grid-tied inverters at the Tucson electric power solar test yard

  • Author

    Brooks, Adria E. ; Fijal, Joshua ; St. Germaine, Michael T. ; Orsburn, Sean ; Greenberg, Jane ; Lonij, Vincent P. A. ; DellaGiustina, Daniella N. ; Cronin, Alexander D.

  • Author_Institution
    Univ. of Arizona, Tucson, AZ, USA
  • fYear
    2013
  • fDate
    16-21 June 2013
  • Firstpage
    2853
  • Lastpage
    2856
  • Abstract
    We measure the conversion efficiencies of six inverters manufactured by Fronius, SMA, and Xantrex. We measure efficiencies ranging from 87.0% to 91.7%. We find differences between manufacturers´ specified efficiency and field performance of -3.8% and -6.0% Inverter efficiencies are also studied as a function of global horizontal irradiance and ambient temperature.
  • Keywords
    invertors; Fronius; SMA; Tucson electric power solar test yard; Xantrex; ambient temperature; conversion efficiencies; efficiency -3.8 percent; efficiency -6.0 percent; efficiency 87.0 percent to 91.7 percent; field performance; global horizontal irradiance; grid-tied inverters; Inverters; Maximum power point trackers; Photovoltaic systems; Sensors; Temperature measurement; Voltage measurement; energy efficiency; inverters; photovoltaic systems;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Photovoltaic Specialists Conference (PVSC), 2013 IEEE 39th
  • Conference_Location
    Tampa, FL
  • Type

    conf

  • DOI
    10.1109/PVSC.2013.6745066
  • Filename
    6745066