DocumentCode :
683324
Title :
Conversion efficiencies of six grid-tied inverters at the Tucson electric power solar test yard
Author :
Brooks, Adria E. ; Fijal, Joshua ; St. Germaine, Michael T. ; Orsburn, Sean ; Greenberg, Jane ; Lonij, Vincent P. A. ; DellaGiustina, Daniella N. ; Cronin, Alexander D.
Author_Institution :
Univ. of Arizona, Tucson, AZ, USA
fYear :
2013
fDate :
16-21 June 2013
Firstpage :
2853
Lastpage :
2856
Abstract :
We measure the conversion efficiencies of six inverters manufactured by Fronius, SMA, and Xantrex. We measure efficiencies ranging from 87.0% to 91.7%. We find differences between manufacturers´ specified efficiency and field performance of -3.8% and -6.0% Inverter efficiencies are also studied as a function of global horizontal irradiance and ambient temperature.
Keywords :
invertors; Fronius; SMA; Tucson electric power solar test yard; Xantrex; ambient temperature; conversion efficiencies; efficiency -3.8 percent; efficiency -6.0 percent; efficiency 87.0 percent to 91.7 percent; field performance; global horizontal irradiance; grid-tied inverters; Inverters; Maximum power point trackers; Photovoltaic systems; Sensors; Temperature measurement; Voltage measurement; energy efficiency; inverters; photovoltaic systems;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Photovoltaic Specialists Conference (PVSC), 2013 IEEE 39th
Conference_Location :
Tampa, FL
Type :
conf
DOI :
10.1109/PVSC.2013.6745066
Filename :
6745066