Bridging in contaminated transformer oil under AC, DC and DC biased AC electric field
Author :
Mahmud, S. ; Chen, Gang ; Golosnoy, I. ; Wilson, G. ; Jarman, P.
Author_Institution :
Electron. & Comput. Sci., Univ. of Southampton, Southampton, UK
fYear :
2013
fDate :
20-23 Oct. 2013
Firstpage :
943
Lastpage :
946
Abstract :
Cellulose particle accumulation under AC, DC and DC biased AC electric field in transformer oil has been investigated in this paper. Different levels of particle concentrations tested with spherical electrode system. Optical microscopic images and conduction current of the particle accumulation process have been recorded during the experiments. A complete bridge of cellulose particles only observed under DC and DC biased AC electric field.
Keywords :
contamination; electric fields; optical microscopy; power transformers; transformer oil; DC biased ac electric field; cellulose particle accumulation; contaminated transformer oil; optical microscopic images; particle accumulation process; particle concentrations; power transformers; spherical electrode system; Bridge circuits; Electric fields; Electrodes; Microscopy; Oil insulation; Power transformer insulation;