Title :
Simulation of distribution of space charge in ±500kV converter transformer in DC tests
Author :
Hongliang Zhang ; Weili Gong ; Liqiang Cao ; Ping Huang
Author_Institution :
Coll. of Electr. Eng. & Inf., Lanzhou Univ. of Technol., Lanzhou, China
Abstract :
In DC withstand test and polarity reversal test, there would be space charge at interfaces of oil-paper insulation in converter transformer, which may excite partial discharge in subsequent tests. So it is important to study distribution of space charge in converter transformer. This paper simulated the distribution of space charge in a ±500kV converter transformer during DC withstand test, polarity reversal test and earth with finite element method. It was studied that the influences of changing resistivities of oil and paper on space charge distribution in ±500kV converter transformer. Based on the calculation of space charge, the study indicates that the ratio of resistivities of oil and paper has a great influence on distribution and release rate of space charge in ±500kV converter transformer.
Keywords :
power transformer insulation; power transformer testing; space charge; transformer oil; DC withstand test; converter transformer; finite element method; oil-paper insulation; polarity reversal test; space charge distribution simulation; Earth; Electric fields; Oil insulation; Power transformer insulation; Space charge; Windings; DC test; converter transformer; distribution of space charge; finite element method; oil-paper; release rate of space charge;
Conference_Titel :
Electrical Insulation and Dielectric Phenomena (CEIDP), 2013 IEEE Conference on
Conference_Location :
Shenzhen
DOI :
10.1109/CEIDP.2013.6748116