DocumentCode :
684131
Title :
Establishing correction factors for the partitioning of furanic derivatives between oil and paper insulation
Author :
Lessard, Marie-Claude ; Jalbert, J. ; Ryadi, Mohamed
Author_Institution :
Hydro-Quebec (IREQ), Varennes, QC, Canada
fYear :
2013
fDate :
20-23 Oct. 2013
Firstpage :
132
Lastpage :
135
Abstract :
This paper deals with the effect of the temperature on the partition of the furanic derivatives between the oil and paper insulation in power transformers. For the five chemical markers studied, due to its highest polarity, the 2-furfurol showed the highest difference compared to the other furanic species. The author´s propose correction equations at 20°C for the normalization of the temperature for the furanic derivatives. These correction factors allow following the real trend of the markers during all the transformer life.
Keywords :
power transformer insulation; transformer oil; correction factors; furanic derivatives; oil insulation; paper insulation; power transformers; temperature 20 degC; Aging; Chemicals; Mathematical model; Oil insulation; Power transformer insulation;