• DocumentCode
    684211
  • Title

    Study on impulse flashover characteristics of polluted insulators under different voltage applied methods

  • Author

    Peng Bo ; Huang Fu-yong ; Zhou Wei-hua ; Tang Mei-yun ; Wang Cheng ; Wang Feng ; Chao Yafeng

  • Author_Institution
    Hunan Electr. Power Corp. Res. Inst., Changsha, China
  • fYear
    2013
  • fDate
    20-23 Oct. 2013
  • Firstpage
    342
  • Lastpage
    346
  • Abstract
    Pollution flashover of insulator strings is one of the most serious natural disasters in transmission line, and it is dangerous to the power grid. The three voltage applied methods of impulse voltage, power frequency pre-voltage and impulse voltage superimposed on power frequency were built to do the research, and influence of power frequency pre-voltage, partial drying effect of power frequency leakage current on impulse flashover characteristics were studied in the paper. For a fixed NSDD, the impulse flashover voltage of three test methods increased with the increasing of ESDD, the positive polarity impulse flashover voltage was lower than that of negative polarity ones. During the process of impulse voltage superimposed on power frequency test method, the power frequency voltage upraise the initial potential of impulse flashover voltage, and it was conducive to the flashover of polluted insulators. During the process of impulse voltage superimposed on power frequency test, drying effect due to power frequency current and power frequency pre-discharge effect were helpful to the form of partial discharge arc, and they provided favorable environments for the flashover of polluted insulators. Pre-discharge of power frequency and drying effect of power frequency current was contributed to the flashover of polluted insulators, and it was more and more clearly with the increasing of pollution, at a special point both pre-discharge of power frequency and drying effect of power frequency current were in a state of equilibrium.
  • Keywords
    arcs (electric); drying; flashover; insulator contamination; leakage currents; partial discharges; power transmission lines; ESDD; NSDD; insulator strings; partial discharge arc; partial drying effect; polluted insulator; pollution flashover; positive polarity impulse flashover voltage; power frequency current; power frequency leakage current; power frequency predischarge effect; power frequency test method; power grid; transmission line; voltage applied method; Electric potential; Flashover; Insulators; Pollution; Power systems; Surface contamination; Impulse Flashover Characteristics partial drying effect; impulse voltage superimposed on power frequency; polluted insulators; power frequency pre-discharge effect;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation and Dielectric Phenomena (CEIDP), 2013 IEEE Conference on
  • Conference_Location
    Shenzhen
  • Type

    conf

  • DOI
    10.1109/CEIDP.2013.6748300
  • Filename
    6748300