DocumentCode :
684230
Title :
A proposal for Hybrid PD sensor identifying absolute distance from PD source
Author :
Yong-Joo Kim ; Hikita, Masayuki
Author_Institution :
Korea Electrotechnol. Res. Inst., Ansan, South Korea
fYear :
2013
fDate :
20-23 Oct. 2013
Firstpage :
1177
Lastpage :
1180
Abstract :
In this paper, the authors proposed a Hybrid PD (AE) sensor which could tell us an absolute distance from PD source. The proposed sensor installed at one fixed position of power transformer tank wall could detect HF signal and ultrasonic one simultaneously. Ignoring faster arrival time of HF signal, an approximated absolute distance from PD source could be derived easily. Moreover, applying time series measurement to the scheme, a pair of PD signals could enable us to discriminate true PD signals from noise spectra. This paper also shows the laboratory experimental results from an oil transformer of 6 kV.
Keywords :
acoustic measurement; partial discharge measurement; power transformer insulation; time series; transformer oil; absolute distance; acoustoelectric measurement; hybrid partial discharge sensor; partial discharge source; power transformer tank wall; time series measurement; transformer oil; ultrasonic signal; voltage 6 kV; Acoustics; Delay effects; Noise; Oil insulation; Partial discharges; Power transformers; Shape;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation and Dielectric Phenomena (CEIDP), 2013 IEEE Conference on
Conference_Location :
Shenzhen
Type :
conf
DOI :
10.1109/CEIDP.2013.6748319
Filename :
6748319
Link To Document :
بازگشت