DocumentCode
721947
Title
The analysis on inner winding stability of power transformer after initial short-circuit and reclosing under short-circuit fault
Author
Sun, X. ; Li, Y. ; Han, F. ; Zhang, B. ; Wang, H.
Author_Institution
Shenyang Univ. of Technol., Shenyang, China
fYear
2015
fDate
11-15 May 2015
Firstpage
1
Lastpage
1
Abstract
Due to inclement weather in recent years, the short-circuit fault cannot be ruled out in a short time on power system, and this make the transformer as the main components of the system will withstand the impact of two consecutive short-circuit current in a short time, which makes the winding disks in the initial short circuit without damage, its residual deformation and vibration situation can meet the requirements of stability of transformer. But with the impact effect of the second short circuit, the coil disks residual deformation and vibration amplitude has increased in order to destroy the coil insulation eventually to make the instability phenomenon occurred as a result the transformer has been damaged. So it is necessary to study coils stability after reclosing occurred in power transformer.
Keywords
coils; power transformer protection; short-circuit currents; transformer windings; coil disk residual deformation; coil insulation; inner winding stability; instability phenomenon; power transformer; short-circuit current; short-circuit fault; vibration amplitude; winding disks; Circuit stability; Power system stability; Power transformer insulation; Stability analysis; Vibrations; Windings;
fLanguage
English
Publisher
ieee
Conference_Titel
Magnetics Conference (INTERMAG), 2015 IEEE
Conference_Location
Beijing
Print_ISBN
978-1-4799-7321-7
Type
conf
DOI
10.1109/INTMAG.2015.7157209
Filename
7157209
Link To Document