DocumentCode
723624
Title
HV very low frequency method for evaluation of 6 kV cable type 6-AYKCY 3×240 parameters changes during the thermal aging
Author
Vary, Michal ; Skorsepova, Terezia Januskovs ; Lelak, Jaroslav ; Ruhnke, Thorsten ; Kubinec, Peter
Author_Institution
Inst. of Power & Appl. Electr. Eng., Inf. Technol. Slovak Univ. of Technol., Bratislava, Slovakia
fYear
2015
fDate
20-22 May 2015
Firstpage
369
Lastpage
372
Abstract
Very low frequency (VLF) method may be used for analysis of changes in the power cables´ dielectric and electrical parameters during the service lifetime. This paper focuses on a more detailed description of this method and VLF method usage in the laboratory measurement conditions of the power cables. In the second part of the paper we specifically focus on this method applied for measuring the dielectric properties of the cable type 6-AYKCY 3×240. The aim was to analyze changes in dissipation factor values of power cables exposed to thermal aging during 135 days period.
Keywords
dielectric properties; power cables; cable type 6-AYKCY; dielectric parameters; dielectric properties; electrical parameters; power cables; thermal aging; time 135 day; voltage 6 kV; Aging; Cable insulation; Frequency measurement; Power cables; Temperature measurement; Voltage measurement; VLF method; diagnostic; power cable; thermal aging;