Abstract :
In many formulations of controller architectures for variable-speed vapor compression machines, evaporator superheat temperature is commonly selected as a regulated variable due to its correlation with cycle efficiency. Further, the superheat temperature setpoint is conveniently taken as a constant value over the wide range of operating conditions. However, direct measurement of superheat is not always available, and estimates of superheat have limited robustness. Therefore identifying alternate signals in the control of vapor compression machines that correlate to efficiency is desired. In this paper, we consider a model-free extremum seeking algorithm that adjusts compressor discharge temperature setpoints in order to optimize energy efficiency. While perturbation-based extremum seeking methods have been known for some time, they suffer from slow convergence rates-a problem emphasized in application by the long time constants associated with thermal systems. Our method uses a new algorithm (time-varying extremum seeking), which has dramatically faster and more reliable convergence properties. In particular, we regulate the compressor discharge temperature using setpoints selected from a model-free time-varying extremum seeking algorithm. We show that the relationship between compressor discharge temperature and power consumption is convex (a requirement for this class of realtime optimization), and use time-varying extremum seeking to drive these setpoints to values that minimize power. The results are compared to the traditional perturbation-based extremum seeking approach. Experiments are performed demonstrating discharge temperature optimization from 72°C to 62°C for a particular set of experimental conditions where the power consumption is decreased from 525 W to 450 W, resulting in an increase in observed coefficient of performance (COP) of 14%.
Keywords :
compressors; convergence; energy conservation; evaporation; machine control; optimal control; optimisation; perturbation techniques; time-varying systems; COP; coefficient of performance; compressor discharge temperature setpoint; convergence rate; cycle efficiency; energy efficiency optimization; evaporator superheat temperature set point; model-free time-varying extremum seeking algorithm; perturbation-based extremum seeking method; power consumption; real time setpoint optimization; temperature 72 degC to 62 degC; thermal systems; variable speed vapor compression machine control; Convergence; Discharges (electric); Heating; Optimization; Power demand; Temperature measurement;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
American Control Conference (ACC), 2015
Conference_Location :
Chicago, IL
Print_ISBN :
978-1-4799-8685-9
Type :
conf
DOI :
10.1109/ACC.2015.7170860
Filename :
7170860
Link To Document :
بازگشت