DocumentCode :
738926
Title :
Active anti-islanding detection based on pulse current injection for distributed generation systems
Author :
Chung-Chuan Hou ; Yu-Chun Chen
Author_Institution :
Dept. of Electr. Eng., Chung Hua Univ., Hsinchu, Taiwan
Volume :
6
Issue :
8
fYear :
2013
fDate :
9/1/2013 12:00:00 AM
Firstpage :
1658
Lastpage :
1667
Abstract :
This study proposes an active anti-islanding detection using an adjustable pulse current for distributed generation systems. The pulse current injection is utilised to find out difference voltage response between utility systems and islanding operation systems within 2.8 ms, which is faster than conventional current injection methods. Furthermore, the power line communication is utilised to keep islanding detection system with accuracy. Finally, the performances of the proposed scheme are validated by simulation and test results.
Keywords :
carrier transmission on power lines; distributed power generation; active anti-islanding detection; adjustable pulse current; difference voltage response; distributed generation systems; islanding operation systems; power line communication; pulse current injection; time 2.8 ms; utility systems;