Diagnostics of a Transformer´s Active Part With Complementary FRA and VM Measurements
Author :
Kornatowski, E. ; Banaszak, S.
Author_Institution :
West Pomeranian Univ. of Technol., Szczecin, Poland
Volume :
29
Issue :
3
fYear :
2014
fDate :
Jun-14
Firstpage :
1398
Lastpage :
1406
Abstract :
This paper presents the concept of complementary measurements with the use of two methods that allow for a more detailed assessment of the mechanical condition of a transformer´s active part. These methods are frequency-response analysis (FRA) and vibroacoustic method (VM). The VM was interpreted separately in steady and transient conditions, thus allowing, together with the FRA measurements, the determination of possible source of vibrations. This paper presents a theoretical introduction, experimental measurements performed on a real transformer with introduced controlled deformations and, finally, an example of a practical application.
Keywords :
acoustic measurement; frequency response; power transformers; vibration measurement; VM measurements; complementary FRA; controlled deformations; frequency-response analysis method; mechanical condition assessment; transformer active part diagnostics; transient conditions; vibration source measurement; vibroacoustic method; Oil insulation; Power transformer insulation; Transformer cores; Vibrations; Windings; Core; frequency response; transformer; vibroacoustic method; windings;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2013.2289944