• DocumentCode
    745781
  • Title

    A novel concept for fault current tolerable contactors

  • Author

    Zhou, Xin ; Little, Michael

  • Author_Institution
    Innovation Center, Eaton Corp., Milwaukee, WI, USA
  • Volume
    28
  • Issue
    4
  • fYear
    2005
  • Firstpage
    710
  • Lastpage
    716
  • Abstract
    It is critical in the development of new contactors and starters to enable the product to avoid or minimize contact welding during short circuit events. The IEC 60947-4-1 or UL 508E Type II coordination requires that a contact weld can be easily broken without significant deformation after short circuit events, and the new standard of IEC 60947-6-2 mandates no contact welds after short circuit events. In this paper, a novel concept has been developed and investigated to allow significant fault current tolerance improvement for next generation contactor and starter product lines. An innovative design of the movable contact bridge utilizes the magnetic force generated by the fault current to "latch" the contacts open until current zero and reclose after current zero. This delay of contact reclosing allows the molten contact surface to solidify and minimizes or even eliminates contact welding altogether. This design does not require a size increase of the product to achieve this performance and adds minimal cost. Test evaluation has been carried out to verify this concept. The test results show that the contacts close about 1.5 to 2ms after current zero and achieve no contact welding after short circuit events with proper current limiting by the upstream circuit protector.
  • Keywords
    contactors; electrical contacts; fault tolerance; magnetic forces; short-circuit currents; contact reclosing; contact weld; fault current tolerable contactor; fault current tolerance; magnetic force; molten contact surface; movable contact bridge; short circuit event; starter product line; test evaluation; type II coordination; upstream circuit protector; Bridge circuits; Circuit testing; Contactors; Costs; Delay; Fault currents; IEC standards; Latches; Magnetic forces; Welding; Contactor; contact-weld; fault-current tolerable; short circuit; starter; type II coordination;
  • fLanguage
    English
  • Journal_Title
    Components and Packaging Technologies, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    1521-3331
  • Type

    jour

  • DOI
    10.1109/TCAPT.2005.859663
  • Filename
    1546178