Abstract :
This paper deals with the electromagnetic transients in transformer substations. The substation can have more than one transformer. Generally, these parallel-connected transformers can be of different sizes and neutral treatment. The substation is fed from a high-voltage overhead transmission line (or cable). Emphasis is given to the substation terminal voltage, the transformers´ neutral voltages (if their neutrals are not directly earthed) as well as the internal distribution of transient voltages along the transformers´ windings, following a typical external double-exponential surge voltage. The distributed parameter transient analysis is done in the s-domain, and then followed by a numerical Laplace inverse transform technique to get the distributions in time domain
Keywords :
Laplace transforms; electromagnetic fields; power overhead lines; power transformers; power transmission lines; substations; surges; time-domain analysis; transformer substations; transformer windings; transient analysis; distributed parameter transient analysis; electromagnetic transients; high-voltage overhead transmission line; neutral treatments; numerical Laplace inverse transform; parallel-connected transformers; s-domain; substation terminal voltage; time domain; transformer sizes; transformer substations; transformer windings; transient voltages distribution; Circuits; Electromagnetic analysis; Electromagnetic transients; Fault currents; Power system transients; Power transformer insulation; Power transformers; Protection; Substations; Transient analysis;
Journal_Title :
Industry Applications, IEEE Transactions on