Abstract :
This paper reviews rating of cables installed in air. The following cable installations are investigated: (1) cables on riser poles, (2) cables in open and closed trays, (3) cables wrapped in fire protection covers, (4) cables in horizontal tunnels, and (5) cables in vertical shafts. The rating of cables in these installations is computed by solving energy balance equations for the unknown surface temperature with a given conductor current. In ampacity computations the conductor current is adjusted iteratively until permissible cable conductor and surface temperatures are achieved. It is shown in the paper how the same energy balance equations can be used to compute the ratings of all the above cable installations
Keywords :
cable sheathing; electric conduits; flameproofing; power cables; ampacity computations; cable ratings; cable shafts; cable trays; cable tunnels; closed trays; conductor current; energy balance equations; fire protection covers; horizontal tunnels; open trays; riser poles; unknown surface temperature; vertical shafts; Cable insulation; Conductors; Equations; Fires; Heat transfer; IEC standards; Protection; Shafts; Temperature dependence; Underground power cables;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.483996
Filename :
483996
Link To Document :
بازگشت