• DocumentCode
    750792
  • Title

    Development of 500 kV DC PPLP-insulated oil-filled submarine cable

  • Author

    Fujimori, A. ; Tanaka, T. ; Takashima, H. ; Imajo, T. ; Hata, R. ; Tanabe, T. ; Yoshida, S. ; Kakihana, T.

  • Author_Institution
    Kansai Electr. Power Co. Inc., Osaka, Japan
  • Volume
    11
  • Issue
    1
  • fYear
    1996
  • fDate
    1/1/1996 12:00:00 AM
  • Firstpage
    43
  • Lastpage
    50
  • Abstract
    This paper outlines the development of a 500 kV DC oil-filled submarine cable capable of transmitting 2800 MW with ±500 kV 2800 A bipole system. Polypropylene laminated paper (PPLP) was employed as the insulation material, which is the world´s first application to DC cables. The conductor size is 3000 mm2, which is the largest size for submarine cables ever put into practical use. Through various fundamental and prototype tests, the cable proved to have excellent electrical characteristics for DC voltage as well as transient overvoltage. The cable and accessories are undergoing a long-term accelerated aging test as the final confirmation of their reliability and stability
  • Keywords
    HVDC power transmission; ageing; composite insulating materials; insulating oils; insulation testing; life testing; organic insulating materials; overvoltage; paper; power cable insulation; power cable testing; power cables; reliability; submarine cables; transient analysis; 2800 A; 2800 MW; 500 kV; DC oil-filled submarine cable; bipole system; conductor size; electrical characteristics; long-term accelerated aging test; polypropylene laminated paper insulation; reliability; stability; transient overvoltage; Cable insulation; Cable shielding; Conducting materials; Conductors; Insulation testing; Materials testing; Oil filled cables; Optical fiber cables; Power cables; Underwater cables;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.483999
  • Filename