• DocumentCode
    750813
  • Title

    Long-term testing of a low-loss 800 kV PPLP insulated SCFF cable

  • Author

    Couderc, D. ; Belec, M. ; Chaaban, M. ; Leduc, J. ; St-Arnaud, R. ; Hata, R.

  • Author_Institution
    IREQ, Varennes, Que., Canada
  • Volume
    11
  • Issue
    1
  • fYear
    1996
  • fDate
    1/1/1996 12:00:00 AM
  • Firstpage
    51
  • Lastpage
    57
  • Abstract
    This paper describes the dielectric and accelerated aging tests on an 800 kV AC polypropylene laminated paper (PPLP) insulated low-loss SCFF cable prototype. The test program was developed to validate the PPLP technology for future Hydro-Quebec 765 kV St-Lawrence under-river crossings. The paper reports on the cable and accessories characteristics, the test line construction, the test program, and the main results obtained. The successfully completed program has shown the overall very good performance of the cable and its accessories
  • Keywords
    ageing; cable jointing; insulation testing; life testing; organic insulating materials; paper; power cable insulation; power cable testing; power cables; 765 kV; 800 kV; AC power cable; Hydro-Quebec 765 kV St-Lawrence under-river crossings; accessories characteristics; cable characteristics; long-term testing; low loss SCFF cable; polypropylene laminated paper insulation; test line construction; test program; Cable insulation; Cable shielding; Conductors; Dielectric losses; Dielectrics and electrical insulation; Oil insulation; Prototypes; Rivers; Testing; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.484000
  • Filename
    484000