• DocumentCode
    752212
  • Title

    Probabilistic method to assess insulating link performance for protection of crane workers

  • Author

    Karady, George G. ; Shah, Minesh ; Dumora, D.

  • Author_Institution
    Arizona State Univ., Tempe, AZ, USA
  • Volume
    11
  • Issue
    1
  • fYear
    1996
  • fDate
    1/1/1996 12:00:00 AM
  • Firstpage
    384
  • Lastpage
    392
  • Abstract
    Contact between cranes and transmission lines is the most frequent cause of accidents, which may lead to electrocution of an operator or rigger. This accident can be prevented by inserting an insulating link in the crane´s cable. This paper analyzes currents during accidents and proposes a modified test method for contaminated insulating links. A new and better insulating link is also introduced. Flashover probability of contaminated insulator links is measured. The test results are evaluated with a new probabilistic method which leads to better assessment of link efficiency. The paper concludes that the risk of link failure cannot be determined without the new flashover probability measurement
  • Keywords
    composite insulators; cranes; electric shocks; flashover; insulator contamination; insulator testing; maintenance engineering; power overhead lines; power transmission lines; probability; accidents; contaminated insulator links; crane worker protection; electrocution; flashover probability; insulating link performance assessment; link failure; modified test method; probabilistic method; Accidents; Cranes; Dielectrics and electrical insulation; Flashover; Pollution; Power cable insulation; Power cables; Protection; Testing; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.484038
  • Filename
    484038