DocumentCode
752212
Title
Probabilistic method to assess insulating link performance for protection of crane workers
Author
Karady, George G. ; Shah, Minesh ; Dumora, D.
Author_Institution
Arizona State Univ., Tempe, AZ, USA
Volume
11
Issue
1
fYear
1996
fDate
1/1/1996 12:00:00 AM
Firstpage
384
Lastpage
392
Abstract
Contact between cranes and transmission lines is the most frequent cause of accidents, which may lead to electrocution of an operator or rigger. This accident can be prevented by inserting an insulating link in the crane´s cable. This paper analyzes currents during accidents and proposes a modified test method for contaminated insulating links. A new and better insulating link is also introduced. Flashover probability of contaminated insulator links is measured. The test results are evaluated with a new probabilistic method which leads to better assessment of link efficiency. The paper concludes that the risk of link failure cannot be determined without the new flashover probability measurement
Keywords
composite insulators; cranes; electric shocks; flashover; insulator contamination; insulator testing; maintenance engineering; power overhead lines; power transmission lines; probability; accidents; contaminated insulator links; crane worker protection; electrocution; flashover probability; insulating link performance assessment; link failure; modified test method; probabilistic method; Accidents; Cranes; Dielectrics and electrical insulation; Flashover; Pollution; Power cable insulation; Power cables; Protection; Testing; Voltage;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.484038
Filename
484038
Link To Document