DocumentCode :
753832
Title :
Evaluation of partial discharge detection techniques on hydro-generators in the Australian Snowy Mountains scheme. Tumut 1 case study
Author :
Simpson, J.W.L. ; Tychsen, R.C. ; Su, Q. ; Blackburn, T.R. ; James, R.E.
Author_Institution :
Snowy Mountains Hydro-Electric Auth., Australia
Volume :
10
Issue :
1
fYear :
1995
fDate :
3/1/1995 12:00:00 AM
Firstpage :
18
Lastpage :
24
Abstract :
An evaluation of partial discharge detection techniques used on the Unit 3 hydroelectric generator stator windings at Tumut 1 power station in the Snowy Mountains scheme of Australia is presented. Measurements were made with an RF slot probe, Robinson ERA Model 5 detector, Ontario Hydro PDA-H detector and a recently developed partial discharge site location (PDSL) system before and after removal of coils. Good agreement was found between all methods with the PDSL system achieving high accuracy in identifying individual high discharging coil sides
Keywords :
hydroelectric generators; insulation testing; machine insulation; machine testing; partial discharges; probes; stators; test equipment; Australia; PDA-H detector; RF slot probe; Robinson ERA Model 5 detector; accuracy; coils; hydroelectric generator; insulation measurements; partial discharge detection techniques; partial discharge site location; power station; stator windings; Australia; Coils; Detectors; Hydroelectric power generation; Partial discharge measurement; Partial discharges; Power generation; Probes; Radio frequency; Stator windings;
fLanguage :
English
Journal_Title :
Energy Conversion, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8969
Type :
jour
DOI :
10.1109/60.372564