DocumentCode
754385
Title
A comparison of UPS for powering hybrid fiber/coaxial networks
Author
Pinheiro, Humberto ; Jain, Praveen K. ; Joós, Géza
Author_Institution
Dept. of Electron. & Comput. Eng., Concordia Univ., Montreal, Que., Canada
Volume
17
Issue
3
fYear
2002
fDate
5/1/2002 12:00:00 AM
Firstpage
389
Lastpage
397
Abstract
Four distinct uninterruptible power supply topologies are presented here for powering hybrid fiber/coaxial (HFC) networks. Topologies based on a low frequency isolation transformer are found to have better efficiency than the topologies with high frequency transformer. However, the latter topologies have much better performance in terms of transient response, quality of the output voltage, input power factor, total harmonic distortion of the input current, size and weight. The series-parallel resonant based UPS topology is found to have best overall performance for the emerging HFC applications
Keywords
cable television; coaxial cables; harmonic distortion; optical fibre networks; power factor; telecommunication power supplies; transient response; uninterruptible power supplies; 60 Hz; UPS; cable TV; high frequency transformer; hybrid fiber/coaxial networks powering; input current; input power factor; low frequency isolation transformer; output voltage quality; series-parallel resonant based UPS topology; total harmonic distortion; transient response; uninterruptible power supply topologies; Coaxial components; Ferroresonance; Frequency; Hybrid fiber coaxial cables; Network topology; Optical fiber devices; Power supplies; Telecommunication network topology; Uninterruptible power systems; Voltage;
fLanguage
English
Journal_Title
Power Electronics, IEEE Transactions on
Publisher
ieee
ISSN
0885-8993
Type
jour
DOI
10.1109/TPEL.2002.1004246
Filename
1004246
Link To Document