• DocumentCode
    754385
  • Title

    A comparison of UPS for powering hybrid fiber/coaxial networks

  • Author

    Pinheiro, Humberto ; Jain, Praveen K. ; Joós, Géza

  • Author_Institution
    Dept. of Electron. & Comput. Eng., Concordia Univ., Montreal, Que., Canada
  • Volume
    17
  • Issue
    3
  • fYear
    2002
  • fDate
    5/1/2002 12:00:00 AM
  • Firstpage
    389
  • Lastpage
    397
  • Abstract
    Four distinct uninterruptible power supply topologies are presented here for powering hybrid fiber/coaxial (HFC) networks. Topologies based on a low frequency isolation transformer are found to have better efficiency than the topologies with high frequency transformer. However, the latter topologies have much better performance in terms of transient response, quality of the output voltage, input power factor, total harmonic distortion of the input current, size and weight. The series-parallel resonant based UPS topology is found to have best overall performance for the emerging HFC applications
  • Keywords
    cable television; coaxial cables; harmonic distortion; optical fibre networks; power factor; telecommunication power supplies; transient response; uninterruptible power supplies; 60 Hz; UPS; cable TV; high frequency transformer; hybrid fiber/coaxial networks powering; input current; input power factor; low frequency isolation transformer; output voltage quality; series-parallel resonant based UPS topology; total harmonic distortion; transient response; uninterruptible power supply topologies; Coaxial components; Ferroresonance; Frequency; Hybrid fiber coaxial cables; Network topology; Optical fiber devices; Power supplies; Telecommunication network topology; Uninterruptible power systems; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Electronics, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8993
  • Type

    jour

  • DOI
    10.1109/TPEL.2002.1004246
  • Filename