DocumentCode :
755811
Title :
New technique for the accurate location of earth faults on transmission systems
Author :
Johns, A.T. ; Moore, P.J. ; Whittard, R.
Author_Institution :
Sch. of Electron. & Electr. Eng., Bath Univ., UK
Volume :
142
Issue :
2
fYear :
1995
fDate :
3/1/1995 12:00:00 AM
Firstpage :
119
Lastpage :
127
Abstract :
A new technique for the single-ended location of resistive earth faults on power transmission lines is presented. Unlike previous work, the algorithm developed has inherent insensitivity to setting errors in the remote source impedance value. This is an important feature, since the remote source impedance often varies significantly under operational conditions. The paper shows the theoretical development of the algorithm, together with a detailed consideration of the hardware aspects. Results are presented for a standard 400 kV transmission line application study
Keywords :
digital simulation; earthing; fault location; power system analysis computing; power transmission lines; software packages; transmission networks; 400 kV; EMTP; algorithm; computer simulation; earth fault location; hardware; power transmission lines; remote source impedance value; setting error insensitivity; transmission systems;
fLanguage :
English
Journal_Title :
Generation, Transmission and Distribution, IEE Proceedings-
Publisher :
iet
ISSN :
1350-2360
Type :
jour
DOI :
10.1049/ip-gtd:19951589
Filename :
372990
Link To Document :
بازگشت