Title :
Comparative analysis between ROCOF and vector surge relays for distributed generation applications
Author :
Freitas, Walmir ; Xu, Wilsun ; Affonso, Carolina M. ; Huang, Zhenyu
Author_Institution :
Dept. of Electr. Energy Syst., State Univ. of Campinas, Brazil
fDate :
4/1/2005 12:00:00 AM
Abstract :
This paper presents a comprehensive comparative analysis between rate-of-change-of-frequency (ROCOF) and vector-surge (VS) relays for distributed generation islanding detection. The analysis is based on the concepts of detection-time versus active power-imbalance curves and critical active power imbalance. Such curves are obtained through dynamic simulations. The performance of these devices considering different scenarios is determined and compared. Factors such as voltage-dependent loads, generator inertia constant, and multidistributed generator systems are analyzed. False operation of these relays due to faults in adjacent feeders is also addressed. Results show that ROCOF relays are more reliable to detect islanding than vector surge relays when the active power imbalance in the islanded system is small. However, ROCOF relays are more susceptible to false operation than VS relays.
Keywords :
distributed power generation; power distribution protection; relay protection; synchronous generators; ROCOF relays; active power imbalance curves; distributed generation islanding detection; generator inertia constant; multidistributed generator systems; power distribution systems; rate-of-change-of-frequency relays; synchronous generators; vector-surge relays; voltage-dependent loads; Digital relays; Distributed control; Distributed power generation; Frequency; Power distribution; Power system relaying; Power system reliability; Surges; Synchronous generators; Voltage; Distributed generation; islanding detection; rate of change of frequency (ROCOF) relays; vector-surge (VS) relays;
Journal_Title :
Power Delivery, IEEE Transactions on
DOI :
10.1109/TPWRD.2004.834869