• DocumentCode
    759805
  • Title

    Effects of heat sinks in metal-oxide surge arresters on ZnO element power dissipation and temperature distribution

  • Author

    Zheng, Zhong ; Nishiwaki, Susumu ; Boggs, Steven ; Fukano, Takato

  • Author_Institution
    Dept. of Electr. & Comput. Eng., Univ. of Toronto, Ont., Canada
  • Volume
    20
  • Issue
    2
  • fYear
    2005
  • fDate
    4/1/2005 12:00:00 AM
  • Firstpage
    1402
  • Lastpage
    1408
  • Abstract
    The cooling effect of heat sinks placed between the ZnO elements of a surge arrester is evaluated in the context of the IEC Type Test for thermal stability using transient nonlinear finite element analysis with coupled thermal and electric fields to simulate the entire operating duty type test sequence in IEC60099-4.
  • Keywords
    arresters; finite element analysis; heat sinks; temperature distribution; thermal stability; zinc compounds; IEC thermal stability test; ZnO; heat sinks; metal-oxide surge arresters; power dissipation; temperature distribution; transient nonlinear finite element analysis; Arresters; Cooling; Heat sinks; IEC; Power dissipation; Resistance heating; Surges; Temperature distribution; Testing; Zinc oxide; Finite element analysis; heat sink; metal oxide surge arrester; thermal stability;