Title :
The effect of ground resistance on secondary arc current on an EHV transmission line
Author :
Shi, Wei ; Li, Fan ; Han, Yanhua ; Li, Yunge
Author_Institution :
Sch. of Electr. Eng., Xi´´an Jiaotong Univ., Shaanxi, China
fDate :
4/1/2005 12:00:00 AM
Abstract :
After a single-phase-to-ground fault occurs on an extremely-high-voltage transmission line, the duration of the secondary arc mainly depends on the magnitude of the secondary, which is determined by the ground resistance and the system´s equivalent impedance at the fault location. In this paper, analytical formulas for calculating the system´s equivalent impedance have been developed for three different arc-extinguishing techniques. These formulas show a satisfactory accuracy in comparison with electromagnetic transient program (EMTP) simulations. Then, the effect of the ground resistance on the secondary arc current has been evaluated by comparing it with the system´s equivalent impedance. The resistance hardly influences the secondary arc current when no arc-extinguishing facility is adopted or when four-reactor banks are employed; while the resistance significantly affects the current when high-speed grounding switches are used.
Keywords :
arcs (electric); earthing; electric impedance; fault currents; high-voltage engineering; power transmission faults; power transmission reliability; transmission network calculations; EHV transmission line; EMTP simulations; arc-extinguishing techniques; equivalent impedance calculation; fault location; ground resistance; power transmission faults; power transmission reliability; secondary arc current; single-phase-to-ground fault; EMTP; Electric resistance; Fault location; Grounding; Impedance; Power system reliability; Power transmission lines; Switches; Transmission lines; Voltage; Fault currents; power transmission faults; resistance; transmission lines;
Journal_Title :
Power Delivery, IEEE Transactions on
DOI :
10.1109/TPWRD.2004.839179