• DocumentCode
    760153
  • Title

    Positive Switching Impulse Discharge Performance and Voltage Correction of 1-m Rod-Plane Air Gap

  • Author

    Hu, Jianlin ; Jiang, Xingliang ; Wang, Shaohua ; Zhang, Zhijin ; Sun, Caixin ; Shu, Lichun ; Wang, Jun

  • Author_Institution
    Coll. of Electr. Eng., Chongqing Univ.
  • Volume
    22
  • Issue
    2
  • fYear
    2007
  • fDate
    4/1/2007 12:00:00 AM
  • Firstpage
    1247
  • Lastpage
    1254
  • Abstract
    Switching impulse discharge performance of air gaps at high altitudes, which is a fundamental in the extremely high voltage external insulation design, remains an unsolved key technology across the world. Due to the limited applicable range of "g" parameter method recommended by IEC Publication 60-1(1989), this paper aims to explore the relationship between positive switching impulse 50% discharge voltage U 50 of rod-plane air gaps and atmospheric parameters, and proposes two new voltage correction methods based on the parameter "g" and the atmospheric pressure ratio, respectively. The two methods have been proved by the experimental investigations carried out on 1-m rod-plane air gap both in the artificial climate chamber and at three spots of different high altitudes in this study. The results show that, if the additional influence of absolute humidity is considered, the positive switching impulse 50% discharge voltage U50 of rod-plane air gaps is a power function of relative pressure and relative air density; the "g" parameter method in IEC Publication 60-1(1989) is not applicable to the regions with an altitude above 2000 m or the condition of h/delta>15 g/m3; compared with the correction method based on the "g" parameter method, the correction method based on relative atmospheric pressure has a wider applicable range and less error; when the absolute humidity increases 1 g/m3 , U50 varies within the range of 1.0%-1.15%
  • Keywords
    air gaps; discharges (electric); humidity; IEC publication; artificial climate chamber; atmospheric pressure ratio; correction method; discharge voltage; high voltage external insulation design; positive switching impulse discharge performance; relative air density; rod-plane air gaps; voltage correction; Air gaps; Educational technology; Error correction; Humidity; IEC standards; Impulse testing; Insulation testing; Sun; Temperature; Voltage; Air gap; atmospheric parameters; correction; high altitude; humidity; impulse discharge;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2007.893622
  • Filename
    4141125