DocumentCode :
760395
Title :
Conducted emissions from FACTS equipment operational within substations $part II
Author :
Stewart, Martin G. ; Siew, W.H. ; Li, Qingmin ; Walker, Keith ; Piner, Chris
Author_Institution :
Dept. of Electron. & Electr. Eng., Univ. of Strathclyde, Glasgow, UK
Volume :
20
Issue :
2
fYear :
2005
fDate :
4/1/2005 12:00:00 AM
Firstpage :
1782
Lastpage :
1787
Abstract :
Electromagnetic interference (EMI) may be caused by the fast switching of thyristors and gate turn-off thyristors (GTOs), which are used in static var compensators (SVCs) and static synchronous compensators (STATCOMs) to control reactive power generation and absorption to and from the transmission system. As a result, high levels of electrical disturbance may be coupled into the electrical ports of auxiliary electronic equipment, and if the levels are above the immunity level of the equipment, maloperation that may lead to a trip can occur. This study sought to measure typical conducted EMI levels in four selected SVC-based and one static synchronous compensator (STATCOM)-based substation. The results and their correlation to the existing IEC 61000-4 EMC Standards series are discussed, and indications of changes to the immunity tests are presented.
Keywords :
electromagnetic compatibility; electromagnetic interference; flexible AC transmission systems; immunity testing; substations; EMI; FACTS equipment; auxiliary electronic equipment; conducted emissions; electrical disturbance; electrical ports; electromagnetic interference; fast switching; gate turn-off thyristors; immunity; maloperation; reactive power generation; static synchronous compensators; static var compensators; substations; thyristors; Automatic voltage control; Control systems; Electromagnetic interference; IEC standards; Immunity testing; Power generation; Reactive power control; Static VAr compensators; Substations; Thyristors; Conducted emissions; electromagnetic immunity; electromagnetic-compatibility (EMC) measurement; static synchronous compensator (STATCOM); static var compensator (SVC);
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2004.834874
Filename :
1413455
Link To Document :